♻️型号:IS215VPROH1B
✳️产品特征:
完全独立安全架构
标准三模冗余 TMR 设计,三块 VPRO 并行运行
双层堆叠一体化 PCB 设计
多路专用测速采集通道
适配 VME 标准机架插槽
⏰交货货期:现货
��WhatsApp:+86 15359298293
��邮箱:lanlan@szcxdcs.com
✈️/��️物流:支持航空/陆运/海运等
质保期:质保一年
联系人:蓝经理
咨询来电:15359298293(微信同号)
GE IS215VPROH1B 独立三重冗余超速保护模块
IS215VPROH1B 是 GE Speedtronic Mark VI 经典涡轮控制系统专用独立三重冗余超速保护核心板卡(VPRO 保护组件)。整套机组保护单元采用三块 VPRO 板(R8/S8/T8)三冗余架构,独立于主控调节系统运行,搭配 TPRO 测速端子板、TREG 跳闸继电器端子板配套使用,负责燃气轮机、蒸汽轮机独立安全保护逻辑,是机组紧急停机 ESD 的核心安全硬件,广泛应用于火电联合循环、燃气电站、炼油透平机组。
模块采用双层堆叠 PCB 结构(底板 + IS200VPRW 上层子板),搭载独立处理器、测速采集回路、跳闸继电器驱动回路与 IONet 以太网通讯接口,不依赖主控 CPU 即可独立完成超速、超温、停机保护运算,实现安全保护与常规控制硬件物理隔离,规避主控故障导致保护失效风险。

GE IS215VPROH1B 独立三重冗余超速保护模块
核心作用


| Parameter Item | Specification |
|---|---|
| Model | IS215VPROH1B |
| Alternative Coated Model | IS215VPROH1BD |
| Compatible Control System | GE Speedtronic Mark VI Turbine Control System |
| Board Structure | Double-layer stacked PCB (Base board + IS200VPRW daughter board) |
| Redundancy Architecture | Triple Modular Redundant (TMR, R8/S8/T8 three independent boards) |
| Main Protection Function | Emergency Overspeed (EOS) trip, ESD emergency shutdown, exhaust over-temperature protection |
| Speed Sensor Input | 6 passive magnetic speed pickup channels |
| Thermocouple Input Channels | 9 thermocouple analog input channels |
| Trip Relay Control | 12 built-in relay drive outputs, 3 groups for 3 trip solenoids |
| Trip Solenoid Power Supply | 125 VDC |
| Communication Interface | IONet Ethernet port for controller & HMI data exchange |
| Supported Protocol | GE proprietary IONet protocol |
| Hot Swappable | Yes, single board replacement without turbine shutdown |
| Matching Terminal Boards | TPRO speed terminal board, TREG trip relay terminal board |
| VME Slot Standard | Standard VME rack slot mounting |
| Diagnostic Indicators | Run, Fault, Network Link, Overspeed Alarm, Relay Status LED |
| Operating Temperature | -20 ℃ ~ +70 ℃ |
| Storage Temperature | -40 ℃ ~ +85 ℃ |
| Power Consumption | Max 15 W per board |
| Net Weight | 0.8 kg |
| Production Status | Discontinued, OEM no longer produces new original units |
| Typical Application | Gas turbine, steam turbine, combined cycle power plant safety pro |